As the Selection of the Gland is totally based on the cable Details, we have made an effort to raise a Selection guide for Glands, for Different cables like Armoured & Unarmoured Cables. We have collected the data of the Few Leading cable Manufactures, & on that we had assumed the Details for different Cables Like for Single Core, Twin Core, Control Cables etc,

 
 
 
Tropodur UnArmoured Three & Half Core Power Cables Type AYY 650 / 1100 V.
No. of Cores & Cross sectional Area Approx. Overall Diameter of Cable SINGLE COMPRESSION TYPE DOUBLE COMPRESSION TYPE
Medium Duty
Heavy Duty (SCG) as per IS 12943 Old SIBG Code I.D. Seal Ring Nipple Entry in Metric Weather Proof Type (CIW) as per BS 6121 Flame Proof Type (CIF) as per IS 2148 Nipple Entry For W/P & FLP.
3 1/2 x 25/16 sm/rm  24.0 CI 1 1/8" SCG 7 (2932) 25 MM 32MM CIW 04A CIF 04A 1 1/4"
3 1/2 x 35/16 sm/rm  25.0 CI 1 1/4" SCG 7 (2932) 25MM 32 MM CIW 04A CIF 04A 1 1/4"
3 1/2 x 50/25 sm 29.0 CI 1 3/8" SCG 8 (2938) 29MM 40 MM CIW 05A CIF 05A 1 1/2"
3 1/2 x 70/35 sm  33.0 CI 1 1/2" SCG 8 (2938) 33 MM 40 MM CIW 06 CIF 06 1 1/2"
3 1/2 x 95/50 sm 38.0 CI 1 3/4" SCG 10 (4251) 38 MM 50 MM CIW 08 CIF 08 2"
3 1/2 x 120/70 sm  41.0 CI 1 3/4" SCG 10 (4251) 42 MM 50 MM CIW 08 CIF 08 2"
3 1/2 x 150/70 sm 44.0 CI 2" SCG 11 (5451) 44 MM 50 MM CIW 09 CIF 09 2"
3 1/2 x 185/95 sm  50.0 CI 2 1/4" SCG 12 (5463) 50 MM 63 MM CIW 010A CIF 010A 2 1/2"
3 1/2 x 240/120 sm  57.0 CI 2 3/4" SCG 14  (6675) 57 MM 75 MM  CIW 012 CIF 012 3" 
3 1/2 x 300/150 sm  63.0 CI 2 3/4"  SCG 14 (6675) 64 MM 75 MM CIW 012 CIF 012 3"
3 1/2 x 400/185 sm 70.0 CI 3 1/4" SCG 16 (7882) 70 MM 82 MM CIW 013 CIF 013 3 1/4"
3 1/2 x 500/240 sm 80.0 CI 3 1/2" SCG 17 - 80 MM 90 MM CIW 014 CIF 014 3 1/2"
3 1/2 x 630/300 sm 87.0 CI 4" SCG 18 - 87 MM 100 MM CIW 015 CIF 015 4"
 