Selection Guide Product Details Certificates Clients    
 
  Back
 
 
   
 
 
 
   
 
Indoor or outdoor gland for single wire armoured cables
 
 
     
 
  Application  
 

Wether Proof Glands are used in regular Climatic Conditions, Which are Water Proof & Dust Proof (IP 67). With the Protection of PVC Hood it can be used in Different Areas.


 
  Parts of Glands  
 

1) Check Nut, 2) Washer, 3) Nipple Entry Part, 4) Neoprene Inner Rubber, 5) Armour Clamping cone, 6) Armour Clamping Ring, 7) Main Gland Body, 8) Neoprene Outer Rubber, 9) Skid Washer, 10) Gland Cover. As all the metal parts are made of brass, as per the Approved Drawing


 
  Certificates  
 

Type Test Report from Regional Testing Center as per
BS 6121, with IP 67
No. RTC / WR/ ELEC / 64/ 0304/319 Dt.25/05/03


 
  Accessories  
 
PVC Hood, Earth Tag, Stopping Plug, Reducers,
Adaptors, etc are Available with Specified Dimensions, In Accordance to the Gland, Separately.


 
 
  Fitting sequence  
 


a) Insert Part No. 10, 9, 8, & 7 respectively on the Outer Sheath of the cable before Exposing the Armour,

(b) After Removing Over Sheath of the Cable, Insert Part No.6 over the Exposed Armour

(c) Size Armour length, lift Armour, & Insert Part No.5 under the Armour, Taper Part facing inward Side, Squeeze Part No.5, by pushing Part No. 6, towards it,

(d) Insert Part No. 4& 3 on inner sheath,
Than tight part No.3 with Part No.7, & Tight Part
No. 10 with Part No.7.

(d) Finally Apply the full fitted Gland in the Encolsure with the Entry Thread Provided, if The Enclosure does not have thread than tight the gland with the Part No. 1 Provided.

 
 
 
 
      Our Products are Certified By